Model 933A Portable Power Sentinel™

Model 933A Portable Power Sentinel™

Arbiter's accurate and affordable portable power quality meter, with PMU compatible functions measuring synchrophasors, time, harmonics, flicker, K-factor, interruptions, phase and frequency.

Model 933A User Manual
Download PDF(4.2 MB) »

Model 933A Portable Power Sentinel™ Data Sheet
Download PDF(71.5 kB) »

Model 933A Portable Power Sentinel™ Data Sheet Espanol
Download PDF(76.8 kB) »

The perfect field analyzer for the power quality engineer, Model 933A Portable Power Sentinel™ is the most accurate and affordable portable power quality meter in the industry. The proprietary EnergyDSA™ Digital Signal Analysis algorithms allow the user to measure or record harmonics, flicker (per IEC 61000-4-15, PST and Instantaneous), K-factor and interruptions. The data logging capabilities allow the user to specify which data to log as well as when to log the data, continuously or when user specified thresholds are exceeded.

Time, Phase and Frequency Capabilities

Model 933A has the ability to also measure system time, phase, frequency and phasors. When synchronized using the IRIG-B IEEE-1344 unmodulated input or the GPS input, the Model 933A is capable of accurate revenue metering and synchrophasor analysis per the IEEE-1344. Pre-fault data is buffered for a half second allowing for accurate fault recording and event driven data analysis. The host processor and the DSP each have 128 MB of memory which provides ample space for data storage

Portability

Thanks to the high level of integration made possible with EnergyDSA™, this unit combines multiple capabilities into one compact, light weight instrument. Weighing less than 5.8 kg (12.8 lbs), the Portable Power Sentinel™ is a power quality monitor, a data and event logger, a system monitor, and a revenue meter designed to accompany you wherever you go and operate continuously for a full eight-hour shift.

  • Measures and records harmonics, flicker, K-factor, interruptions
  • Support for synchrophasor measurements
  • Optionally measures system time, phase, frequency and phasors
  • Can be synchronized via IRIG-B IEEE-1344 unmodulated input or GPS input
  • 320 x 240 graphic LCD display
  • 30 key multifunction keypad
  • RS-232 cable included
  • RS-232 or USB 1.1 port
  • External power supply or Battery operated (NiMH, with 8 hours typical run time)

Input/Output

Configuration

3Ø:

3-element, 2½-element, 2-element, selectable

1Ø:

2-element, 1½-element, 1-element, selectable

Voltage

Range (3Ø/1Ø)

1 to 650 Vrms, selectable (phase-to-phase for 2 and 2½-element; phase-to-neutral for 1 and 3-element)

Overrange

1200 V peak, nominal

Current

Model 933A-01 20 Amp direct input module:

Range (3Ø/1Ø)

0.05 to 20 Arms, selectable, per element

Low Range

1 mA to 1 Arms

Overrange

40 A peak, nominal (maximum continuous input current: 20 Arms per element, all ranges

VA, W, VAR

Range

Any voltage, current and number of elements within the specified limits

Compensation

CT and PT

Both magnitude and phase compensation, CT with 12 point nonlinear interpolation

Transformer

Both iron and copper loss

Frequency

Range

45 to 65 Hz, for specified accuracy

Harmonics

to 3 kHz

Inputs

Voltage

Safety banana plugs

Current

5-way binding posts (Model 933A-01)

Insulation

400 volts, nominal, to neutral/chassis, surge voltage class III
600 volts, nominal, to neutral/chassis, surge voltage class II

Power Quality

Harmonics Measurement

Standard

2nd to 50th (50 or 60 Hz) per IEC 61000-4-7, 100 ms overlapping data window

Measurements

THD, K-factor, rms harmonic current and voltage, rms harmonic current and voltage with K-factor compensation (each harmonic magnitude is multiplied by the square of the harmonic number before summing), individual magnitude and phase

Logged Data

Selectable, may be regularly logged or registered. Event-logged also available when user-specified limits are exceeded

Interruptions Logged Data

Selectable, may be regularly logged or registered. Event-logged also available when user-specified limits are exceeded.

Flicker

Standard

Per IEC 61000-4-15, PST and Instantaneous

Logged Data

Selectable, may be regularly logged or registered. Event-logged also available when user-specified limits are exceeded.

Limit Alarms

Functions

Upper or lower limits may be set on most measured functions. Limits may also be set on maximum imbalance (ratio of Zero and Negative Sequence Components to Positive Sequence)

Output

Via system interface and display

Accuracy/Specifications

Accuracy Note

Accuracy specifications include all sources of uncertainty. Except as noted, specifications apply for the full operating range, including temperature (-10° to +50° C), line voltage, input range including specified overrange, power factor, input frequency, and drifts over a one-year calibration interval. Specifications assume synchronization to GPS and operation in 3-element mode or in a well-balanced system where imbalance does not degrade accuracy.

Watts

0.05% of reading, for voltage 7 to 650 Vrms and current 10 mA to 20 Arms and PF > 0.2

Vrms

0.05% of reading or ±5 mV, whichever is greater. (For voltage 50 to 650 Vrms and current 50 mA to 20 Arms)

Arms

0.05% of reading or ±0.1 mA, whichever is greater. (For voltage 50 to 650 Vrms and current 50 mA to 20 Arms)

Phase Angle, Ø

Ø: 0.01°, phase-to-phase or voltage-to-current (For voltage 50 to 650 Vrms and current 50 mA to 20 Arms)
0.2% (current 10 to 50 mArms)

Ø underrange: 0.05° of reading (current 10 to 50 mArms)

VA, VAh

0.05% of reading (For voltage 50 to 650 Vrms and current 50 mA to 20 Arms)
0.1% (current 10 to 50 mArms)

VAR, VARh

same as W, Wh except replace PF with (1-PF2)0.5

Power Factor

0.0002 · sin (Ø) (For voltage 50 to 650 Vrms and current 50 mA to 20 Arms)
0.001 · sin (Ø) (current 10 to 50 mArms)

Harmonics

0.1% THD or 5% of reading, whichever is greater

Frequency

< 1 ppm (0.0001%) of reading, 50 or 60 Hz nominal, plus timebase error

System

Phase

0.03° + [timebase error · 360° · frequency] (With GPS Option)

Time

1 µs + timebase error (With GPS Option)

Event Inputs

±10 µs (typical)

Flash Memory Data Storage

Host Processor

Capacity

128 MB. See Operation Manual for record length and capacity calculations

Data

All functions measured and totalized by Model 933A; each record is stored with a time tag

Storage Rate

Selectable
Event data stored upon occurrence

Lifetime

100,000 storage cycles minimum

Data Retention

Indefinite; no power or battery is required to retain data

DSP Processor

Capacity

128 MB; about 1000 seconds or 17 minutes

Data

Primary waveform

Storage Rate

10240 samples per second (approximately 170 samples per cycle). Fixed 30 cycles pre-fault data. Event data stored to Host Processor flash memory upon occurrence. User has same triggers as the Host Processor flash and can select the maximum fault duration, post fault recording time, and retrigger on/off.

Lifetime

100,000 storage cycles minimum

Data Retention

Indefinite; no power or battery is required to retain data

System Control and Monitoring

System Time, Phase and Frequency

System Time

Unlimited accumulation with ±1 µs resolution

Frequency

6 digits, xx.xxxx Hz

System Phase

0 to 360° with 0.01° resolution

Phasors

Standard

Per IEEE Standard 1344 or PSCSV

Rate

20 measurements/second

Interface

Operator

Display

320 x 240 graphic LCD display with CCFL Backlight

Keyboard

30 keys: 5 soft function, 7 dedicated function, 5 cursor control, power on/off and 12 key numeric key pad

Communications

Serial

RS-232, RJ-11 modular connector

USB

Version 1.1, B-Type receptacle

Protocols

Proprietary

PowerSentinelCSV 933 (PSCSV933)

Synchronization

IRIG TTL-Level Shift

TTL-Level Shift per IEEE-1344 as output from an Arbiter Systems Model 1084B

General/Remote

Optional Remote GPS receiver available. See Accessory AS0077600

GPS Tracking

GPS-L1 (1575.42 MHz); 12 channel (tracks up to 12 satellites)

GPS Acquisition

2 minutes typical

GPS Accuracy

UTC-USNO ±1 µs (only need 1 satellite with correct position)

GPS Out of Lock

Via system interface and status display; optional, via contact closure

Timebase Error

GPS Locked

Less than 1 µs, when locked to at least one satellite with correct position

Unlocked

10 ppm, typical, after being locked for 10 minutes minimum

IRIG-B

Less than 1 µs + accuracy of IRIG-B source

General

Physical

Size

205 x 305 x 225 mm (8 x 12 x 8.8 in.)
483 x 483 x 305 mm (16 x 16 x 12 in.), shipping

Weight

5.8 kg (12.8 lbs), maximum
9.1 kg (20 lbs), shipping

Environmental

Temperature

Operating: -10° to +50° C
Nonoperating: -40° to +75° C

Humidity

Noncondensing

Power Requirements

Internal Battery

Type

NiMH

Operation

Eight hours typical

Charging

Four hours

Stand by Use

5 VA typical

External Power

Range

85 to 264 Vac, 47 to 63 Hz or 120 to 275 Vdc, 25 VA typical when charging battery, 5 VA typical standby use

Input

IEC connector with fuse; surge withstand per ANSI C37-90.1 and IEC801-4 standard

There are no additional Options for this product

See Accessories tab for additional components available

Included
AP0007700 Modular DB9 to RJ11 Adapter, Preconfigured
AS0074100 Input Module - CT Input current module with 5-way Connectors
CA0023600 RJ-11 Cable Four-pin crossed, 7 ft
PD0031100 Operation Manual (933A)
P01R-P10R Country specific power cord with right angle female end
Country specific plug and power cord cable with right angle female end
Available
09311A 400 Amp 20:1 Precision CT, 0.1% Accuracy
Extends the outstanding accuracy, features, and performance of Models 931A, 930A and 929A by increasing the current input capability to 400 amperes. Available on Models 931A, 930A, and 929A.
811AT 3-Phase Univ. Test Plug Current Lead Set
812H Safety Ground Lead
813AT 3-Phase Safety Voltage Lead Set
816AT 3-Phase Spade-Lug Current Lead Set
AP0001300 1000:1 Clamp-on CT, 1000 A (Current Output)
AP0006700 CT, Clamp-On, 3000 Amp, 660V, Elliptical Opening (Current Output)
AP0010200 CT, Clamp-On, 1000 Amp, 1000:5,Elliptical Opening (Current Output)
AP0010300 CT, Clamp-On, 600 Amp, 100:1 (Current Output)
AP0012300 1 100:1 Clamp-on CT, 150 A (Voltage Output)
AP0012800 AC Current Probe, Clamp-On, 1000:1 (Current Output)
AS0076500 Input Module - CT input current module with banana Connectors.
Uses standard shrouded banana jacks.
AS0076700 Input Module – CT input current module with audio connectors
Requires use of CA0027100 or CA0027200, available separately.
AS0077600 Remote GPS Receiver with mounting bracket and 15 m (50 ft.) cable
AS0076601 GPS Remote Receiver; DB15
AS0077700 Programmable KYZ Contacts and Event Inputs
AS0079001 Universal Test Plug Current Shunt, A Phase Red
AS0079002 Universal Test Plug Current Shunt, B Phase Yellow
AS0079003 Universal Test Plug Current Shunt, C Phase Blue
CA0027100 2 CT Cable, Current Output
CA0027200 2 CT Cable, Voltage Output
CA0029000 Cable, Shielded, Shrouded Banana to Unshrouded Banana, 6ft
CA0029800 Receiver Cable Extender 7.6 m (25 ft.)

1  Requires CA0027200
2 Required with Option 03