Model 931A Power System Analyzer

Model 930A Three Phase Power Analyzer

Model 929A Three Phase Power Meter

931A front panel
Optional equipment may be shown.

with Power DSA Digital Signal Analysis

Arbiter Systems®, Inc. Models 931A, 930A, and 929A, with state-of-the-art PowerDSA™ Digital Signal Analysis, make more measurements, more accurately, more easily, and at a lower price than ever before. Basic accuracy of 0.05% of reading and 0.05° phase, harmonic analysis, and full three-phase capability are standard on all three models. The 930A and 931A also incorporate full two way serial communication for use in power quality trend monitoring, and for complete power system analysis the 931A also includes a transducer calibration and timer features.

The Arbiter Systems®, Inc. Model 930A Three Phase Power Analyzer is an economical alternative to the Model 931A Power System Analyzer when the dc voltage measurement, transducer calibration and timer features are not required. The Model 930A has the same ac accuracy as the Model 931A with PowerDSA™ Digital Signal Analysis. The Model 930A with serial communication capability and available application software, in conjunction with a laptop computer, is a valuable tool for use in power quality trend monitoring, as well as being a complete diagnostic tool for use in the substation and industrial power environment.

The Arbiter Systems®, Inc. Model 929A Three Phase Power Meter is an economical alternative to both the Model 931A Power System Analyzer and the Model 930A Three Phase Power Analyzer when serial communication, dc voltage measurement, transducer calibration and timer features are not required. The Model 929A has the same ac accuracy as the Model 931A with PowerDSA™ Digital Signal Analysis, and is a complete diagnostic tool for use in the substation and industrial power environment.

Portability

Thanks to the high level of integration made possible with PowerDSA™, our instruments are lighter, smaller, and run longer on a charge than any others in this class. Smaller than a lunchbox and weighing only 5.8 kg (12.8 pounds), you can take any of our PowerDSA™ instruments with you wherever you go, operate it continuously for a full 8-hour shift from its internal sealed lead-acid battery, and then recharge it completely in eight hours.

Safety

Built in a rugged, non-conductive high-impact polyethylene case, and with all inputs isolated from instrument common by transformers, optical isolators or high-value series resistors, these instruments were designed with safety in mind. A front-panel ground terminal provides a sink for leakage currents.

SAFETY NOTICE: Grounding the Model 931A Power System Analyzer:

Convenience

The outstanding features do not end with light weight, measurement flexibility, or unprecedented accuracy. Many other user conveniences have been added to ease your workload.

Options and Accessories

Available options include an additional 16 megabytes of internal data memory to provide storage for data logging (not available for the Model 929A), 931A Application Software, 930A Application Software, an adjustable tilt handle/bail assembly for the transit case.

Available accessories include a 400 Amp 20:1 precision CT, mounting brackets to provide for mounting of CT's inside the cover of the transit case, a wide selection of test leads, and an RS-232 cable.

All of this, and more, is ready to help you do your job better and in less time. Put an Arbiter Systems® Model 931A, Model 930A, or Model 929A, all with PowerDSA™ Digital Signal Analysis to work for you soon!

Basic Measurements

The 931A, 930A, and 929A measure all of the basic quantities: true-rms voltage and current, frequency and phase angle. PowerDSA™ analysis measures these quantities more accurately than ever before. Accuracy is 0.05% for voltage and current and 0.05° for phase.

The proprietary PowerDSA™ narrow-band mode even measures the fundamental signal alone, rejecting the effects of harmonics and noise. In wide-band mode, the effects of all harmonics and noise are included. Phase angle is always true, fundamental phase, and frequency is accurate even with large harmonics causing multiple zero crossings. Accuracy is never degraded, even with real-world signals.

1-phase volts/amps
1-phase frequency and degrees
1-phase graphical display

Power Quantities

The PowerDSA™ instruments measure power quantities, too, with accuracy unprecedented for a lightweight, portable instrument. Measurements are made in accordance with IEEE standards, including the effects of harmonics and reactive power. Watts (W), watthours (Wh), volt-amperes (VA), volt-ampere hours (VAh), volt-amperes reactive (VAR), volt-amperes reactive hours (VARh), and power factor (PF): PowerDSA™ analysis measures them all, with 0.11% basic accuracy. 1-phase apparant power

Harmonics

Measure harmonics and view the results graphically; as summary numbers, such as total harmonic distortion (THD), even harmonic distortion (EHD), odd harmonic distortion (OHD) or K-factor; or as individual harmonic amplitude and phase. The bandwidth extends to over 3 kHz for accurate measurement to the 50th harmonic on 50 or 60 Hz systems, now you can know for sure what is really happening on your system. harmonics

Waveform Display

You can view the signal waveforms for both channels on the high contrast 240x64 graphic display. Both channels are normalized to Channel 1 fundamental phase, so you can see, for example, the relationship between current waveform distortions and voltage phase. waveform

Timer

(Model 931A)
The Model 931A's timer/counter (not available on the Model 930A/929A) measures relay operating times or elapsed test times, or counts input rates and events. View times in seconds or in terms of power-line cycles. Both inputs are independently opto-isolated for safety and flexibility.
timer results

Three-Phase Measurement

The 931A, 930A, and 929A include a full three-phase input section, for automated three-phase measurement sequences. PowerDSA™ analysis measures two signals at a time, and the results are combined into four complete three-phase displays.

You can select from the following three-phase display modes:

  • Basic three-phase display
    View voltage, current, phase, frequency and power quantities on one convenient display.
  • Vector display
    View voltages, currents and phase angles with their vector representation.
  • Voltage/Current Sequence display
    View voltage, current and phase along with positive, negative and zero sequence values.
  • Energy display
    View voltage, current, phase, frequency and energy quantities on one convenient display.

As a power trend monitor and recording system, these PowerDSA™ instruments can verify phase relation, phase rotation, power direction, load balance and positive, negative, and zero sequence of voltage and/or current as well as calibrating and verifying in-service performance of Disturbance, Fault and Transient Recorders.

3-phase power
3-phase vector
3-phase sequence components
3-phase energy

Transducer Calibration

(Model 931A)
The outstanding accuracy of the Model 931A with PowerDSA™ is ideal for transducer calibration. The Model 931A includes the necessary dc voltage and current measurements to accurately measure transducer outputs, using a separate, opto-isolated input section. With only an external source or load box, or when making in-service measurements, the Model 931A provides complete field transducer calibration.
transducer

CT/PT Ratios

Correction factors for external CTs and/or PTs, can be entered to display the measured results in input-side units. You can even measure ratios using the instrument's CH1/CH2 function. This example shows a nominal 200:1 (or 1000:5) current ratio; if Channel 1 is a CT burden voltage and Channel 2 CT secondary current, the result is the loop resistance in ohms. ct/pt ratios

Extended Measurement Ranges

For greater accuracy, the Model 09311A Auxiliary CT allows measurement of signals up to 400 amps with total basic accuracy of 0.1%. This CT mounts directly to the Model 931A, 930A, or 929A current input connectors and may be used for one two or three of the current inputs, depending on your needs. extended measurement ranges

Model 931A Specifications

Input:

Basic Inputs & Measurements:
The Arbiter Systems® Model 931A Power System Analyzer has two main measurement channels, Channel 1 and Channel 2. Any voltage or current input signal may be selected for either channel. For basic measurements (voltage, current, frequency, phase angle) any combination of inputs may be used. For power and energy measurements (active power, apparent power, reactive power and power factor), one voltage and one current must be selected. For three-phase measurements, the input configuration is selected automatically, based on the measurement type (for example, 3-phase 4-wire 3-element).
Voltage:
Input Range  1.5 to 750 Vrms (underrange to 200 mV) [2 to 1000 Vdc (Model 931A Only)]
Inputs  Four; A, B, C, N
Phase-to-Phase
Phase-to-Neutral
Phase-to-Synthesized Neutral (A+B+C / 3)
Impedance  1 megohm
Leakage  < 3.5 mA per IEC348 and UL1244
Current:
Input Range  0.04 to 20 Arms (underrange to < 1 mA)
Inputs  Three; A, B, C, plus synthesized neutral
Burden  0.01 ohm maximum
Isolation  Transformer, 1000 Vrms
Neutral  Synthesized, -(A+B+C)
Timer: (Model 931A Only)
Inputs  Two; 4 to 300 Vdc; 20 to 300 Vrms; or dry contact/thyristor output
Isolation  Optical, 300 Vrms, each channel
Transducer: (Model 931A Only)
Range  0 to 1, 0 to 100 mAdc and 0 to 10 Vdc
Protection  Overvoltage to 120 V, both inputs
Isolation  Optical, 300 Vrms

Measurements:

Voltage and Current:
Method  Wideband: True rms, 3 kHz Bandwidth
Narrowband: Fundamental magnitude
Accuracy  0.05% of reading
Underrange  < 1% of reading, typical at 0.3 mArms
DC voltage (Model 931A only)  0.1% of reading + 25 mVdc, typical
Phase Angle:
Input  Channel 1 to Channel 2
Range  0 to 360° or ±180°
Accuracy  0.05°
Underrange  < 1°, typical at 0.3 mArms
Frequency:
Input  Channel 1
Range  20 to 500 Hz (underrange to 5 Hz)
Accuracy  0.005% of reading
Harmonics:
Input  Channel 1 or Channel 2
Range  2nd to 50th Harmonic (50 or 60 Hz fundamental)
Accuracy  5% of THD reading + 0.01%
Display  THD; K-factor; Amplitude bar graph; and individual harmonic magnitude and phase (simultaneous)
Waveform:
Display  Channel 1 and/or Channel 2
Power / Energy Quantities:
Range  0 to 99999 MVA or MVAh
±99999 MVAR or MVARh
±99999 MW or MWh
±1.0000 PF, lead or lag
Accuracy  0.11% of VA, for VA, VAR, and W, 0.001 PF
Transducer (Model 931A Only):
Accuracy  0.05% of reading + 0.01% range
Timer (Model 931A Only):
Range  0.0001 to 9999.9 seconds, or 0.01 to 999999 cycles
Accuracy  0.005% of reading + 1 digit
AC Trigger  Add 1 ms maximum, 0.15 ms at 120 Vrms

Interface:

Operator Interface:
Display  240x64 graphic LCD with cold-cathode fluorescent lamp (CCFL) backlight
Keyboard  21 function keys plus On/Off
Memory  EEPROM (calibration data)
Battery backup RAM (setup and stored results)
Real-time clock
Data  Instrument calibration data
User setups (up to six)
Logged data (15 to 200); time-tagged
System Interface (Model 931A and 930A Only):
RS-232  1200 to 115,200 baud; 7 or 8 data bits; 1 or 2 stop bits; even/odd/no parity
Isolation  Optical, 300 Vrms

Power Requirements:

Internal Battery:
Type  Sealed lead-acid
Operation  8 hours typical
Charge  8 hours typical; fast + float charge
External Power:
Range  85 to 264 Vac, 47 to 440 Hz, 15 VA maximum
110 to 250 Vdc, 15 W maximum
Safety  Designed to meet UL, CSA, VDE

General:

Physical:
Size  205 x 305 x 225 mm (8 x 12 x 8.75 in.)
483 x 483 x 483 mm (16 x 16 x 16 in.), shipping
Weight:  5.8 kg (12.8 lbs), net
8.2 kg (18 lbs), shipping
Environmental:
Operating Temperature  -10° to +50° C
Nonoperating Temperature  -40° to +75° C
Humidity  Noncondensing

Options:

Order Number: Description
930Aopt01: 16 MB memory
931Aopt01: 16 MB memory

Accessories:

Included:

Order Number: Description
812H: Safety Ground Lead
CA0019806: RS-232 Null Modem Cable, DB9F-DB9F, 2 m (6 ft) length
P01R-P10R: Power Cord (More information)
PD0017400: 931A Operation Manual
PD0024400: 929A/930A Operation Manual

Available:

Order Number: Description
09311A: 400 Amp 20:1 Precision CT, 0.1% Accuracy
811AT: Three-Phase Universal Test Plug Current Lead Set
813AT: Three-Phase Safety Voltage Lead Set
816AT: Three-Phase Spade-Lug Current Lead Set
AP0009800: 100:1 Clamp-on CT, 100 A
AS0035901: Adjustable Tilt Handle/Bail Assembly
AS0036000: 400 Amp CT Bracket (each)
AS0060000: PowerCSV
AS0060100: Single-Phase Clamp-On CT Test Lead

Right Angle Power Cord styles:

No.   Country Specification Rating
P01R Cont Europe CEE7/7 220V
P02R Aust/NZ/PRC AS 3112-1981 240V
P03R U.K. BS 1363 240V
P04R Denmark Afsnit 107-2-01 240V
P05R India BS 546 220V
P06R Israel SI 32 220V
P07R Italy CEI 23-16-VII 1971 220V
P08R Switzerland SEV 1011.1959 220V
P09R N America
and ROC
NEMA 5-15P
CSA C22.2 #42
120V
P10R Japan JIS8303 120V

POWERCSV SOFTWARE

Enhance the performance of your Model 931A Power System Analyzer or Model 930A Three Phase Power Analyzer with the new PowerCSV software (order number AS0060000). The PowerCSV software allows a computer, via the serial port, to import and view data from the extended memory of the Models 931A and 930A. The PowerCSV also has the ability to export a comma-delineated file of the data for easy viewing in any spreadsheet program.

Requires that the Optional 16 MB of Internal Data Memory is installed.

The PowerCSV software is available on our web site: www.arbiter.com.

powercsv_screenshot.gif

16 MB Internal Data Memory

Add another useful feature to the Models 931A and 930A with the 16 MB Internal Data Memory option (order number 931Aopt01 and 930Aopt01). The 16 megabytes of storage space can turn the Models 931A and 930A into stand alone Trend Monitors. The characteristic flexibility of the Model 931A Power System Analyzer and the Model 930A Three Phase Power Analyzer is incorporated into the 16 MB Internal Data Memory options allowing for custom and user friendly configuration.

When equipped with the Extended Memory option, the 931A and 930A can be configured to log data at a set interval, on a valid timer trigger (Model 931A only), when the front panel log key is pressed or via the RS-232 LOG command. Two different types of data sets are available for storage, normal and custom. Normal data sets include four data modes:

The Custom data set allows the user to select any combination of the thirty available individual parameters to log. Record size is dependent on the selected parameters.

The logged data can be reviewed from the front panel of the Models 931A and 930A or downloaded via the RS-232 port to a computer. Exported data can be easily incorporated into a spreadsheet or word processor for inclusion into reports. The PowerCSV Application Software is a useful tool to transfer the data stored in the internal memory to a computer.