Model 1133A Power Sentinel™

  • Synchronized via GPS
  • Revenue Accuracy: 0.025%
  • Power Quality: Harmonics, Flicker, Interruptions
  • Phasor Measurements for Stability & Flow Analysis
  • System Time & Frequency Deviation
  • Internal Data/Event Logging
  • Two Year Warranty
1133A front panel
Optional equipment may be shown.
1133A front panel

with  EnergyDSA Digital Signal Analysis

Take a bite out of power problems and lost revenue with the Arbiter Systems®, Inc. Model 1133A Power Sentinel™ multi-function measurement unit. Combining six functions into one compact, 44 mm (1.75 inch) tall unit, the Model 1133A offers unprecedented accuracy, flexibility, and features.

Revenue Metering

With utility deregulation, accurate energy measurement is increasingly important. For the first time, Arbiter Systems®, Inc. combines state-of-the-art measurement techniques, proprietary EnergyDSA™ technology, and the accurate, cost-effective time synchronization of our precision GPS clock products in the Model 1133A Power Sentinel™ multi-function measurement unit. The Model 1133A brings laboratory performance to the substation, delivering unprecedented revenue accuracy of 0.025% under most conditions. Compare this to traditional watt-hour meters which are limited to an accuracy of no better than 0.1% in the lab, with increasing errors as conditions depart from the ideal (see figures).figures).

The Model 1133A measures revenue more accurately than any meter ever before. The difference between 0.025% and 0.1% is surprising. With many transmission lines wheeling thousands of megawatts of power, the difference in accuracy of 0.075% translates to hundreds of thousands of dollars over a year's time. Even at lower power levels, improved accuracy yields significant revenue enhancement.

Power Quality Monitoring

The Model 1133A's features only begin with its outstanding accuracy in energy measurement. Our proprietary EnergyDSA™ digital signal analysis algorithms provide you with more information than ever before. You can measure harmonics and K-factor, flicker, interruptions, and log data by time interval, or record out-of-limit events with time of occurrence. You can set limits on any quantity. Also, an alarm contact may be activated, or a dial-up modem call initiated.

System Control and Monitoring

The Model 1133A measures system (absolute) phase angle, system frequency deviation, and system time deviation. See the white paper Absolute Phase[PDF~26.1 kB] Phasor measurement data in accordance with IEEE Standard 1344, at a rate of 20/second, is standard. This data allows for sophisticated, real-time monitoring and control of stability and power flow is now practical. These measurements are made possible with the Model 1133A's internal GPS synchronization.

Synchronization

A built-in Global Positioning System (GPS) satellite receiver synchronizes your Model 1133A within 1 µs of Coordinated Universal Time (UTC), which may also be converted to your local time. With synchronization, revenue data can be accumulated in time slots as short as one minute. Other substation equipment, such as digital fault recorders, solid-state relays, remote terminal units, and programmable logic controllers, may be synchronized with the standard IRIG-B unmodulated timecode output. This output has sufficient power to drive numerous loads, for example, 40 Schweitzer™ SEL-321 relays.

Data and Event Logging

Sixteen megabytes of flash memory are provided standard, upgradable to 32 MB. This non-volatile memory can record revenue data, power quality, internally-detected faults, alarms, events, and external events. Four optically-isolated event inputs may be used to monitor external events.

Technology

Arbiter Systems' many years of experience making accurate measurements of ac signals and providing state-of-the-art timing equipment lies at the heart of the Model 1133A Power Sentinel™ revolutionary performance. For example, built-in, real-time autocalibration eliminates many sources of error which would otherwise degrade accuracy. This process measures the output of an internal calibration source, time-multiplexed along with the input signals. A complete set of calibration measurements is executed once each second. By passing the calibration signal through the same measurement circuits as the input signals, drift in component values, temperature sensitivities, and many other errors are completely removed.

This design approach minimizes the number of components that can affect accuracy. Therefore, we can afford to use the best available components in those critical applications. Accuracy is (in a simplified fashion) the sum of the imperfections of all of the components that can degrade performance; therefore, by using a small number of highly-accurate parts, accuracy is maximized. This is a simple idea, but implementing it properly requires years of experience.See the white paper What is Accuracy? [HTML or PDF~46.0 kB].

Of course, all of the accuracy in the world means nothing if the resulting signal cannot be processed with equal or better performance. Our proprietary EnergyDSA™ Digital Signal Analysis, an optimized version of the PowerDSA™ analysis developed over the last decade and in use in our Model 931A Power System Analyzer for several years, delivers this performance. We have optimized EnergyDSA™ analysis for the specific requirements of revenue metering and on-line power analysis: speed, accuracy and low cost. Our EnergyDSA™ algorithms measure signals with accuracies characterized not in percent, but in parts per million.

1133A accuracy charts

Model 1133A Specifications

1133A rear panel
Optional equipment may be shown.

1133A rear panel

Input:

Configuration:
  3-element, 2½-element, 2-element, selectable
  2-element, 1½-element, and 1-element, selectable
Voltage:
Range (3Ø/1Ø)  0 to 69, 120, 240, or 480 Vrms, selectable (phase-to-phase for 2 element; phase-to-neutral for 2½ and 3 element)
Overrange  88, 175, 350 or 700 Vrms, nominal
Current:
Range (3Ø/1Ø)  2.5, 5, 10 or 20 Arms, selectable, per element
Overrange  2.9, 5.9, 11.7, or 23.5 Arms, nominal (maximum continuous input current: 20 Arms per element)
VA, W, VAR:
Range  Product of rated voltage and current ranges and number of elements (2½ (3Ø) and 1½ (1Ø) element, use 3 and 1, respectively)
Compensation:
CT and PT  Both magnitude and phase compensation, CT with 12 point nonlinear interpolation
Transformer  Both iron and copper compensation
Frequency:
Range  45 to 65 Hz, for specified accuracy
Harmonics  To 3 kHz
Inputs:
Connections  Removable screw-clamp terminal block, accepting 0.2 to 4 mm2 (AWG 24 to 10) solid or stranded conductors
Insulation  400 volts, nominal, to neutral/chassis, surge voltage class III
600 volts, nominal, to neutral/chassis, surge voltage class II
Contact factory for more detailed information

Interface:

Operator:
Status LEDs  Operate (green), Time Set (green), Alarm (red), Fault (red)
Display  2 x 20 character LCD display
Keyboard  8 key for status and setup
Communications:
Serial Port 1  RJ-11 modular connector
RS-232 (1133opt10)
RS-422/485 half-duplex (1133opt11)
Modem (V.34bis, 33.6k) (1133opt12)
Serial Port 2  RJ-11 modular connector
RS-232 (1133opt20)
RS-422/485 half-duplex (1133opt21)
Modem (V.34bis, 33.6k) (1133opt22)
Ethernet  One RJ-45 modular connector
10Base-T per IEEE 802.3i
Protocols:
Proprietary  PowerSentinelCSV (PSCSV)
Standard  DNP3.0, MODBUS, PQ-DIF
Programmable Contact Outputs:
Type and Number  Form C (SPDT), four (4) sets
Connections  Pluggable 12-pole 5 mm terminal strip, with four, 3-pole mating connectors included
Rating  250 Vac/125 Vdc, 8 A maximum, 2000 VA/150 W maximum
Isolation  4000 Vrms for 1 minute to chassis
Optional KYZ (solid state) contact isolation: 3750 Vrms Input/Output
Functions, Selectable  Programmable Load Control, with preset times or via system interface
Fault Fail-safe (faulted with power off)
Alarm Fail-safe
Out-of-Lock Fail-safe
One Pulse per Hour; contacts closed for one minute at top of hour
Optional KYZ contacts
Other Functions, as required
Event Inputs:
Type and Number  Four, optically-isolated 24 to 240 Vdc (may be configured for 5 volt logic level)
Connections  Pluggable 8-pole 5 mm terminal strip, with four, 2 pole mating connectors
Isolation  4000 Vrms for 1 minute to chassis
Resolution  1 µs

Flash Memory Data Storage:

Capacity  16 megabytes standard (32 MB optional); number of records stored depends on data items selected. See Operation Manual for record length and capacity calculations
Data  Selectable from all functions measured and totalized by the Model 1133A; each record is stored with a time tag
Data Retention  Indefinite; no power or battery is required to retain data
Storage Rate  Selectable; default is 15 minutes. Other intervals as short as one minute may be selected. Event data stored upon occurrence.
Lifetime  100,000 storage cycles minimum

Accuracy Specifications:

Note: Accuracy specifications include all sources of uncertainty. Except as noted, specifications apply for the full operating range, including temperature (-10° to +50° C), line voltage, input range including specified overrange, power factor, input frequency, and drifts over a one-year calibration interval. Specifications assume synchronization to GPS and operation in 3-element mode or in a well-balanced system where imbalance does not degrade accuracy.
Accuracy:
Watts, Wh  0.025% of reading, 10% of range or greater and PF > 0.2
0.005% of VA for PF < 0.2
Underrange  0.0025% of range, below 10% of range
VA, VAh  Same as W, Wh except no PF effect
VAR, VARh  Same as W, Wh except replace PF with (1 - PF2)0.5
Vrms  0.02% of reading or 0.002% range, whichever is greater
Arms  0.03% of reading or 0.003% range, whichever is greater
V2h  0.04% of reading or 0.004% range, whichever is greater
A2h  0.06% of reading or 0.006% range, whichever is greater
Phase Angle, Ø  0.01°, phase-to-phase or voltage-to-current, 10% of range minimum
Power Factor  0.0002 · sin (Ø), 10% of range minimum
Harmonics  0.05% THD or 5% of reading, whichever is greater
Frequency  < 1 ppm (0.0001%) of reading, 50 or 60 Hz nominal, plus timebase error
System Phase  0.03° plus [timebase error · 360° · frequency]
System Time  1 µs plus timebase error
Event Inputs  ±10 µs (typical)

Power Quality:

Harmonics Measurement:
Standard  Per IEC 6000-4-7, 100 ms overlapping data window
Measurements  THD, K-factor, rms harmonic current and voltage, rms harmonic current and voltage with K-factor compensation (each harmonic magnitude is multiplied by the square of the harmonic number before summing), individual magnitude and phase
Logged Data  Selectable, may be regularly logged or registered; or event-logged when user-specified limits are exceeded
Interruptions:
Logged Data  Selectable, may be regularly logged or registered; or event-logged when user-specified limits are exceeded
Flicker:
Standard  Per IEC 61000-4-15, Pst and Instantaneous
Logged Data  Selectable, may be regularly logged or registered; or event-logged when user-specified limits are exceeded
Limit Alarms:
Functions  Upper or lower limits may be set on most measured functions. Limits may also be set on maximum imbalance
Output  Via system interface and display or contact closure

System Control and Monitoring:

System Time, Phase and Frequency:
System Time  Unlimited accumulation with ±1 µs resolution
Frequency  7 digits, xx.xxxxx Hz
System Phase  0 to 360° with 0.01° resolution
Effect of DC & Harmonics  None; Rejected by narrowband digital filtering
Phasors:
Standard  Per IEEE Standard 1344 or PSCSV
Rate  20 measurements/second

Synchronization:

General:
Tracking  GPS-L1 (1575.42 MHz); 8 channel (tracks up to 8 satellites)
Acquisition  2 minutes typical
Accuracy  UTC-USNO ±1 µs (only need 1 satellite with correct position)
Out-of-Lock  Via system interface and status
Indication  Display; optionally via contact closure
Antenna Characteristics:
Mounting  0.75 inch NPT pipe thread (1 inch - 14 marine type) mount
Dimensions  77.5 dia. x 66.2 mm (3.05 x 2.61 inch)
Weight  170g (6.0 oz.)
Connections  F-type
Cable  15 m (50 ft) included; longer cables optionally available
Synchronization Output:
Type  One; IRIG-B000 or IRIG-B003 per IEEE Std. 1344 (unmodulated or level-shift); 200 mA peak; pluggable 5 mm terminal strip with mating connector, two-pole
Timebase Error:
GPS locked  Less than 1 µs, when locked to at least one satellite with correct position
Unlocked  10 ppm, typical, after being locked for 10 minutes minimum (< 1 second/day unlocked, typical)

Certifications and Approvals:

Compliance to IEC-687 International Standard for Alternating Current Static Watthour Meter for Active Energy
Compliance to IEEE C37.118 Standard for Synchrophasors for Power Systems
Certificate of Conformance to NIST
CE mark/label and certificate

Power Requirements:

Voltage  85 to 264 Vac, 47 to 63 Hz or 120 to 275 Vdc, 5 VA typical
Input  Terminal strip with fuse; surge withstand per ANSI C37-90.1 and IEC801-4 standard

General:

Physical:
Size  1 RU (430 mm W x 44 mm H) rack mount or tabletop; 260 mm deep FMS. Rack mounts included.
508 x 381 x 203 mm (20 x 15 x 8 in.), shipping
Weight  2 kg (4.5 lbs), net
5.5 kg (12 lbs), shipping
Environment:
Temperature, Operating  Standard: -10° to +50° C
Temperature, Nonoperating  -40° to +85° C
Humidity  Noncondensing

Ordering Information:

Power Sentinel™ Multi-Function Measurement Unit:
(Order Number:  Description)
1133A  (LEDs, display and keyboard)

I/O Options:

Order Number: Description
1133opt07: IRIG-B input: Replaces GPS receiver

I/O - Port 1:

Order Number: Description
1133opt10: RS-232
1133opt11: RS-422/485 half-duplex
1133opt12: Modem (V.34bis, 33.6k)

I/O - Port 2:

Order Number: Description
1133opt20: RS-232
1133opt21: RS-422/485 half-duplex
1133opt22: Modem (V.34bis, 33.6k)

Power:

Order Number: Description
1133opt03: Terminal Power Strip, Surge Withstand, 85 to 264 VAc, 110 to 275 Vdc
1133opt04: Terminal Power Strip, Surge Withstand, 10 to 60 Vdc

General:

Order Number: Description
1133opt01: 16 MB memory
1133opt02: Upgrade to 32 MB memory
1133opt05: Mechanical output relays
1133opt06: Solid-State output relays (KYZ)

Accessories:

Included:

Order Number: Description
AS0028200: Rack Mount Kit
AS0058400: 1133A Operation Manual
AS0076200: GPS Antenna, pipe mountable
CA0021315: 15 m (50 ft) RG-6 Antenna Cable
CN0019202: Mating Connectors, 5 mm 2-pole(5 each)
CN0019303: Mating Connectors, 5 mm 3-pole(4 each)
CN0030004: Mating Connector, Voltage Input
CN0030006: Mating Connector, Current Input

Available:

Order Number: Description
AS0044600: GPS Antenna Mounting Bracket
AS0044700: 21 dB Pre-Amp, In Line - For use with cable lengths greater than 75 m (250 ft)
AS0044800: RG-11 Crimp Tool + 25 F-type Connectors
AS0048900: Antenna Grounding Block Kit
AS0049000: GPS Surge Protector Kit
AS0062000: High Interference GPS Antenna and Mounting Adapter Kit
CA0021315: 15 m (50 ft) RG-6 Antenna Cable
CA0021330: 30 m (100 ft) RG-6 Antenna Cable
CA0021345: 45 m (150 ft) RG-6 Antenna Cable
CA0021360: 60 m (200 ft) RG-6 Antenna Cable
CA0021375: 75 m (250 ft) RG-6 Antenna Cable
TF0006400: RG-6 Crimp Tool
WC0004900: 300 m (1000 ft) Roll RG-11 Cable

See GPS Satellite-Controlled Clocks for detailed description of available accessories.