Skip to main content.

Model 936A Reference Current Transformer

936A front panel
Optional equipment may be shown.

The Arbiter Systems®, Inc. Model 936A Reference Current Transformer provides laboratory grade accuracy in a small, portable, ruggedized case, making it ideal for field use. Multiple ratios of 1200:5, 1000:5, 800:5, 600:5 are selectable via a front panel switch. The guaranteed accuracy over the full input range and operating conditions is 0.02% ratio and 0.01° phase (traceable to NIST), ideal for calibrating other current transformers.

The Model 936A uses an active transformer to achieve the high accuracy needed for a primary reference. This design incorporates a dual core toroid with an amplifier aided second stage. The active circuitry reduces the sense transformer core flux to zero and produces an accurate output current independent of burden. The Model 936A was designed primarily for use with the Model 935A Current Source and the Model 931A Power System Analyzer to calibrate current transformers used with the Model 1133A Power Sentinel. The Model 936A's multiple ratio selections allow other current transformers to be tested and calibrated across their entire operating range.

Model 936A Specifications

Input:

Input Range  1 to 1200 Arms
Current Ratios  1200:5, 1000:5, 800:5, 600:5

Output:

Current  5 Arms maximum
Voltage  8.5 Vrms maximum

Power Requirements:

External Power:
Range  85 to 264 Vac, 47 to 440 Hz, 15 VA maximum or 110 to 250 Vdc, 15 W maximum
Safety  Designed to meet UL, CSA, VDE Standard
Inlet  IEC-320 with fuse and mating cordset. Specify P01-P10.

General:

Physical:
Case Size  205 x 305 x 225 mm (8 x 12 x 8.75 in.)
483 x 483 x 483 mm (16 x 16 x 16 in.), shipping
Weight  5.8 kg (12.8 lbs) maximum
Current Transformer  55 mm (2.125 in.) ID Nominal, 3 m (10 ft) cable length
Environmental:
Temperature, operating  0° to +40° C
Temperature, nonoperating  -40° to +85° C
Humidity  Noncondensing